SIMH FE180 PH120

Place of use

They are used at the places where the system and equipment have to funtion for 180 mınutes. They are used as constant control and feeder cables at the environments where the ambiental temperature is high. It is not recommended that the cable functions in motion.

Structure

Inner Conductor

Electrolytic Stranded Copper Wire Class 5
EN 60228, IEC 60228, VDE 0295

Insulation

Silicone Compound EI2

Stranding

Cores Twisted in Layers

Seperator

Glass Fiber Tape

Outer Sheath

Silicone Compound EM9, Terra-cotta

 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


CONDUCTOR
RESISTANCE

INSULATION
RESISTANCE

CURRENT CARRYING
CAPACITY

OPERATING
VOLTAGE

TEST
VOLTAGE

BENDING
RADIUS

TEMPERATURE
RANGE

 
 

mm²

Ω/km

MΩxKm

mm²

A

300/500 V

2000V

10XD

-60ºC +180ºC

 

0.50

39

≥ 100

0.50

9

 

0.75

26

0.75

12

 

1.00

19.50

1.00

15

 

1.50

13.30

1.50

18

 

2.50

7.98

2.50

25

 

4.00

4.95

4.00

34

 

6.00

3.30

6.00

44

 

10.00

1.91

10.00

61

 
                               

FLAME  TEST

FLAME RETARDANT TEST

SMOKE DENSITY TEST

TEST ON CORROSIVENESS
OF COMBUSTION GASES

HALOGEN
FREE TEST

INSULATION INTEGRTY TEST
(FE 180)
(FE 180)

CIRCUIT INTEGRITY WITH SHOCK TEST               (PH)

 
 

IEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
BS EN 60332-1-2

IEC 60332-3-24
VDE 0482-332-3-24
EN 60332-3-24
EN 60332-3-24

IEC 61034-2
VDE 0482-1034-2
EN 61034-2
BS EN 61034-2

IEC 60754-2
VDE 0482-267-2-3
EN 50267-2-3
BS EN 50267-2-3

IEC 60754-1
VDE 0482-267-2-1
EN 50267-2-1
BS EN 50267-2-1

IEC 60331-23                     VDE 472-814

EN 50200                     VDE 0482-200

 
 
 
                             

 

 

Catalog Info